Engineering summary
How to turn raw datalogger counts from an infrasound sensor into pressure: ADC resolution and offset give volts, sensor sensitivity in mV/Pa gives pascals, with a 24-bit, 50 mV/Pa worked example.
In short: To convert infrasound counts to pascals, first convert the datalogger's raw counts to voltage using the ADC offset, maximum count and full-scale voltage range, then divide the voltage by the sensor sensitivity in V/Pa. For a 24-bit ADC with a ±2.5 V range (offset 8,388,608 counts) and a 50 mV/Pa sensor, a reading of 10,000,000 counts corresponds to roughly 0.48 V, or about 9.58 Pa.
In the world of environmental and geophysical monitoring, infrasound sensors play a pivotal role in detecting low-frequency sound waves emanating from natural or man-made sources. These sensors capture invaluable data that can be used for monitoring volcanoes, detecting avalanches, or even tracking artificial explosions.
However, the raw data from these sensors, often stored in digital counts by dataloggers, require conversion into physical units (Pascals) to be meaningful for analysis and interpretation. This article provides a comprehensive guide on how to perform this crucial conversion.
Understanding the Signal Path
The journey of an infrasound signal from physical pressure changes to digital data involves several stages, including the sensor itself, potential preamplification, and finally, analog-to-digital conversion (ADC) by a datalogger. Each stage influences how the final digital count corresponds to the actual pressure change it represents.
Key Components
1. Sensor Sensitivity: Defined typically in V/Pa or mV/Pa, this parameter indicates how much voltage change the sensor produces for a given pressure change. It’s a fundamental characteristic that varies between sensor models.
2. Datalogger ADC Resolution: The ADC’s role is to convert the analog voltage signal from the sensor into digital counts. The resolution of the ADC (e.g., 16-bit, 24-bit, 32-bit) determines the granularity of this conversion, affecting the precision of the digital data.
Conversion Steps
The process of converting digital counts to Pascals involves two main steps
- From Counts to Voltage: First, the raw count values are converted to voltage using the formula:

Here, the ADC Offset is the count value for 0 V input, ADC Max Count are based on the ADC’s bit resolution, and Voltage Range is the full-scale voltage range the ADC can measure.
- From Voltage to Pressure: Next, the voltage is converted to pressure using the sensor’s sensitivity:

This step requires careful attention to unit consistency, especially when converting mV to V.
Practical Example
Let’s go through a clear example of converting digital count values from a datalogger connected to an infrasound sensor into physical pressure units (Pascals). This example will illustrate the step-by-step process using hypothetical yet realistic values for an infrasound monitoring setup.
Example Setup:
- Infrasound Sensor Sensitivity: 50 mV/Pa (millivolts per Pascal)
- ADC Resolution: 24-bit
- Voltage Range of the ADC: ±2.5V (total range 5V)
- Raw Count Value from Datalogger: 10,000,000 counts
- ADC Max Counts: The maximum count value for a 24-bit ADC is 2^24=16,777,216 counts.
- ADC Offset: For a bipolar signal range (±2.5V), the offset (the count corresponding to 0V) is half of the ADC’s maximum count, which is 16,777,216/2=8,388,608 counts.
Step 1: Convert Counts to Voltage
First, we convert the raw count value to voltage using the formula:

Step 2: Convert Voltage to Pressure
Now, we convert the voltage to pressure using the sensor’s sensitivity:

In this example, a raw count value of 10,000,000 from the datalogger corresponds to a pressure change detected by the infrasound sensor of approximately 9.58 Pascals. This process demonstrates how to translate the digital data captured by a datalogger into meaningful physical measurements, allowing researchers and technicians to analyze and interpret infrasound signals accurately.
Important Note: Calibration factors not discussed here (e.g., corrections for frequency response, temperature effects) might also be necessary depending on the precision required for your application. Always refer to the sensor and datalogger manuals for the exact parameters and formulas relevant to your specific setup.
Conclusion
Converting digital counts from an infrasound sensor datalogger to Pascals is a critical step in processing and analyzing infrasound data. Understanding the sensor’s sensitivity and the ADC’s characteristics is essential for accurate conversion. This guide provides a foundational approach for researchers and technicians working in fields where precise environmental monitoring is crucial. By following these steps, one can transform raw digital counts into meaningful physical measurements, unlocking the potential to analyze and interpret infrasound signals for various applications.
Click QuakeLogic infrasound sensors for our infrasound web pages for your infrasound sensor and software needs.
Questions? Contact us at support@quaklogic.net
Key Takeaways
- Step 1: Voltage = (Counts − ADC Offset) / ADC Max Counts × Voltage Range, where the offset is the count for 0 V input.
- Step 2: Pressure (Pa) = Voltage / Sensitivity (V/Pa); convert mV/Pa to V/Pa first to keep units consistent.
- A 24-bit ADC has 16,777,216 counts; for a bipolar ±2.5 V range the zero offset is 8,388,608 counts.
- Worked example: 10,000,000 counts with a 50 mV/Pa sensor and 5 V total range yields approximately 9.58 Pa.
- Frequency response, temperature corrections and manufacturer calibration factors may also be needed for high-precision work.
Frequently Asked Questions
Converting infrasound datalogger counts to pascals takes two steps. First, convert counts to voltage: subtract the ADC offset (the count for 0 V), divide by the ADC's maximum count, and multiply by the full-scale voltage range. Second, divide that voltage by the sensor sensitivity expressed in volts per pascal. Keep units consistent, converting mV/Pa to V/Pa before dividing.
For a 24-bit ADC, the maximum count is 2^24 = 16,777,216. With a bipolar ±2.5 V input range, 0 V falls at the middle of the count range, so the ADC offset is 16,777,216 / 2 = 8,388,608 counts. The total voltage span is 5 V. Subtracting this offset from a raw reading gives the signed count that maps to positive or negative voltage.
A sensitivity of 50 mV/Pa means the infrasound sensor produces 50 millivolts of output for every 1 pascal of pressure change at its input. To convert measured voltage to pressure, divide by 0.05 V/Pa. In the worked example, a datalogger reading of 10,000,000 counts converts to about 0.48 V, which divided by 0.05 V/Pa gives approximately 9.58 Pa of pressure change.
Dataloggers store infrasound signals as digital counts that depend on the ADC's resolution and voltage range, not on the physical pressure wave. Those counts cannot be compared between instruments or against thresholds until they are expressed in pascals. Conversion using the ADC parameters and sensor sensitivity turns the record into true pressure values that researchers can use for volcano, avalanche or explosion monitoring.
Often yes. The basic counts-to-pascal conversion assumes a flat sensor response, but infrasound sensors have a frequency-dependent response and some temperature sensitivity, and any preamplifier gain in the signal path must be included. For precise work, apply the frequency response correction and other calibration factors from the sensor and datalogger manuals, which list the exact parameters for your specific setup.
Related Articles
- What Can Infrasound Detect?
- Infrasound Active Noise Cancellation
- AI Data Centers: Infrasound Noise Monitoring
- AI Data Centers & Low Frequency Noise
Need help with a project? QuakeLogic designs and supplies seismic monitoring, earthquake early warning, structural health monitoring, infrasound, and shake table systems. Browse QuakeLogic products or contact our engineering team with your site, structure, or test requirements.
Related
Reviewed by
QuakeLogic
Published by QuakeLogic engineers and seismic monitoring specialists. QuakeLogic designs earthquake early warning, structural health monitoring, infrasound, vibration monitoring, and shake table testing systems for infrastructure, research, public safety, and industrial engineering teams.
Topic cluster
Related engineering knowledge areas
- Structural Health MonitoringMonitoring for bridges, buildings, dams, tunnels, industrial facilities, and resilient infrastructure.
- Earthquake Early WarningOn-site detection, alerting workflows, seismic switches, and critical infrastructure warning systems.
- Infrasound MonitoringLow-frequency acoustic sensing for environmental noise, blast, UAV, volcano, and defense applications.
- Shake TablesUniaxial, biaxial, vertical, geotechnical, and multi-axis shake table testing systems.
Definitions and references
Terms, standards, and source cues
- SHM: related to Structural Health Monitoring in this QuakeLogic knowledge cluster.
- damage detection: related to Structural Health Monitoring in this QuakeLogic knowledge cluster.
- earthquake early warning: related to Earthquake Early Warning in this QuakeLogic knowledge cluster.
- seismic switch: related to Earthquake Early Warning in this QuakeLogic knowledge cluster.
- infrasound sensors: related to Infrasound Monitoring in this QuakeLogic knowledge cluster.
- low-frequency noise: related to Infrasound Monitoring in this QuakeLogic knowledge cluster.
- shake tables: related to Shake Tables in this QuakeLogic knowledge cluster.
- AC156: related to Shake Tables in this QuakeLogic knowledge cluster.
Next reading
Related engineering articles
Need project support?
Talk with QuakeLogic about monitoring, testing, or warning systems.
Get engineering guidance for seismic monitoring, structural health monitoring, infrasound, vibration, earthquake early warning, and shake table applications.

